ConduitCount

How many #2 THHN fit in 2-1/2" PVC Sch 80?

142 AWG THHN/THWN-2 wires in 2-1/2" Rigid PVC conduit, Schedule 80

4.119 sq in × 40 % = 1.6476 sq in allowed. ÷ 0.1158 sq in per wire = 14.23, so 14.

14 #2 THHN in 2-1/2" PVC Sch 80, drawn to scale

This pull in numbers

14 wires fill
39.4 % of 2-1/2" PVC Sch 80
Limit for three or more
40 %
For 15 or more
3" PVC Sch 80, up to 22
Pipe to wire diameter
5.96 to 1
In THW insulation
12 fit
In XHHW-2 insulation
14 fit

Before you pull 14

#2 THHN in other 2-1/2" conduit

#2 THHN in other PVC Sch 80 sizes

Other wire sizes in 2-1/2" PVC Sch 80

Charts