173 AWG THHN/THWN-2 wires in 2-1/2" Rigid PVC conduit, Schedule 80

4.119 sq in × 40 % = 1.6476 sq in allowed. ÷ 0.0973 sq in per wire = 16.93, which Note 7 rounds up to 17 because the decimal is 0.8 or more.

17 #3 THHN in 2-1/2" PVC Sch 80, drawn to scale

This pull in numbers

17 wires fill
40.2 % of 2-1/2" PVC Sch 80
Limit for three or more
40 %
For 18 or more
3" PVC Sch 80, up to 26
Pipe to wire diameter
6.51 to 1
In THW insulation
14 fit
In XHHW-2 insulation
17 fit

Before you pull 17

#3 THHN in other 2-1/2" conduit

#3 THHN in other PVC Sch 80 sizes

Other wire sizes in 2-1/2" PVC Sch 80

Charts