ConduitCount

How many #1/0 THHN fit in 3-1/2" PVC Sch 40?

211/0 AWG THHN/THWN-2 wires in 3-1/2" Rigid PVC conduit, Schedule 40

9.737 sq in × 40 % = 3.8948 sq in allowed. ÷ 0.1855 sq in per wire = 21.00, which Note 7 rounds up to 21 because the decimal is 0.8 or more.

21 #1/0 THHN in 3-1/2" PVC Sch 40, drawn to scale

This pull in numbers

21 wires fill
40.0 % of 3-1/2" PVC Sch 40
Limit for three or more
40 %
For 22 or more
4" PVC Sch 40, up to 27
Pipe to wire diameter
7.24 to 1
In THW insulation
17 fit
In XHHW-2 insulation
21 fit

Before you pull 21

#1/0 THHN in other 3-1/2" conduit

#1/0 THHN in other PVC Sch 40 sizes

Other wire sizes in 3-1/2" PVC Sch 40