How many #1 THHN fit in 1-1/2" PVC Sch 80?
41 AWG THHN/THWN-2 wires in 1-1/2" Rigid PVC conduit, Schedule 80
1.711 sq in × 40 % = 0.6844 sq in allowed. ÷ 0.1562 sq in per wire = 4.38, so 4.
This pull in numbers
- 4 wires fill
- 36.5 % of 1-1/2" PVC Sch 80
- Limit for three or more
- 40 %
- For 5 or more
- 2" PVC Sch 80, up to 7
- Pipe to wire diameter
- 3.31 to 1
- In THW insulation
- 3 fit
- In XHHW-2 insulation
- 4 fit
Before you pull 4
- The ground counts. Every wire in the pipe counts toward fill, the green or bare ground and the neutrals too. 4 is the total, not the hots.
- Derating. If all 4 were current-carrying, each would be adjusted to 80 % of its ampacity (Table 310.15(C)(1)): a #1 THHN at 145 A in the 90 °C column becomes 116 A. Grounds don't count as current-carrying. How derating works
- Bends. A full pipe pulls hard. Keep to 360° of bends between pull points, less for a tight fill.
#1 THHN in other 1-1/2" conduit
| Conduit | Inside area | Most #1 THHN |
|---|---|---|
| Electrical metallic tubing | 2.036 | 5 |
| Intermediate metal conduit | 2.225 | 5 |
| Rigid metal conduit (RMC, GRC) | 2.071 | 5 |
| Rigid PVC conduit, Schedule 40 | 1.986 | 5 |
| Rigid PVC conduit, Schedule 80 | 1.711 | 4 |
| Flexible metal conduit (FMC, Greenfield) | 1.858 | 4 |
| Liquidtight flexible metal conduit (LFMC) | 1.981 | 5 |
| Electrical nonmetallic tubing (smurf tube) | 1.986 | 5 |
#1 THHN in other PVC Sch 80 sizes
Other wire sizes in 1-1/2" PVC Sch 80
#14: 70#12: 51#10: 32#8: 18#6: 13#4: 8#3: 7#2: 6#1: 4#1/0: 3#2/0: 3#3/0: 1#4/0: 1250 kcmil: 1300 kcmil: 1350 kcmil: 1500 kcmil: 1