ConduitCount

How many #1 THHN fit in 1-1/2" PVC Sch 80?

41 AWG THHN/THWN-2 wires in 1-1/2" Rigid PVC conduit, Schedule 80

1.711 sq in × 40 % = 0.6844 sq in allowed. ÷ 0.1562 sq in per wire = 4.38, so 4.

4 #1 THHN in 1-1/2" PVC Sch 80, drawn to scale

This pull in numbers

4 wires fill
36.5 % of 1-1/2" PVC Sch 80
Limit for three or more
40 %
For 5 or more
2" PVC Sch 80, up to 7
Pipe to wire diameter
3.31 to 1
In THW insulation
3 fit
In XHHW-2 insulation
4 fit

Before you pull 4

#1 THHN in other 1-1/2" conduit

#1 THHN in other PVC Sch 80 sizes

Other wire sizes in 1-1/2" PVC Sch 80

Charts