ConduitCount

How many #2 THHN fit in 1-1/2" PVC Sch 80?

62 AWG THHN/THWN-2 wires in 1-1/2" Rigid PVC conduit, Schedule 80

1.711 sq in × 40 % = 0.6844 sq in allowed. ÷ 0.1158 sq in per wire = 5.91, which Note 7 rounds up to 6 because the decimal is 0.8 or more.

6 #2 THHN in 1-1/2" PVC Sch 80, drawn to scale

This pull in numbers

6 wires fill
40.6 % of 1-1/2" PVC Sch 80
Limit for three or more
40 %
For 7 or more
2" PVC Sch 80, up to 10
Pipe to wire diameter
3.84 to 1
In THW insulation
5 fit
In XHHW-2 insulation
6 fit

Before you pull 6

#2 THHN in other 1-1/2" conduit

#2 THHN in other PVC Sch 80 sizes

Other wire sizes in 1-1/2" PVC Sch 80

Charts