ConduitCount

How many #1 THHN fit in 1-1/2" IMC?

51 AWG THHN/THWN-2 wires in 1-1/2" Intermediate metal conduit

2.225 sq in × 40 % = 0.8900 sq in allowed. ÷ 0.1562 sq in per wire = 5.70, so 5.

5 #1 THHN in 1-1/2" IMC, drawn to scale

This pull in numbers

5 wires fill
35.1 % of 1-1/2" IMC
Limit for three or more
40 %
For 6 or more
2" IMC, up to 9
Pipe to wire diameter
3.77 to 1
In THW insulation
4 fit
In XHHW-2 insulation
6 fit

Before you pull 5

#1 THHN in other 1-1/2" conduit

#1 THHN in other IMC sizes

Other wire sizes in 1-1/2" IMC

Charts