How many #1/0 THHN fit in 1-1/2" PVC Sch 80?

31/0 AWG THHN/THWN-2 wires in 1-1/2" Rigid PVC conduit, Schedule 80

1.711 sq in × 40 % = 0.6844 sq in allowed. ÷ 0.1855 sq in per wire = 3.69, so 3.

3 #1/0 THHN in 1-1/2" PVC Sch 80, drawn to scale

This pull in numbers

3 wires fill
32.5 % of 1-1/2" PVC Sch 80
Limit for three or more
40 %
For 4 or more
2" PVC Sch 80, up to 6
Pipe to wire diameter
3.04 to 1
In THW insulation
3 fit
In XHHW-2 insulation
3 fit

The pipe is 3.04 times the wire's diameter, inside the 2.8 to 3.2 range where three wires can wedge side by side on a pull. If you pull exactly three, go up a size or pull with care.