ConduitCount

How many #1 THHN fit in 3-1/2" PVC Sch 80?

221 AWG THHN/THWN-2 wires in 3-1/2" Rigid PVC conduit, Schedule 80

8.688 sq in × 40 % = 3.4752 sq in allowed. ÷ 0.1562 sq in per wire = 22.25, so 22.

22 #1 THHN in 3-1/2" PVC Sch 80, drawn to scale

This pull in numbers

22 wires fill
39.6 % of 3-1/2" PVC Sch 80
Limit for three or more
40 %
For 23 or more
4" PVC Sch 80, up to 29
Pipe to wire diameter
7.46 to 1
In THW insulation
18 fit
In XHHW-2 insulation
22 fit

Before you pull 22

#1 THHN in other 3-1/2" conduit

#1 THHN in other PVC Sch 80 sizes

Other wire sizes in 3-1/2" PVC Sch 80

Charts