331 AWG THHN/THWN-2 wires in 4" Rigid metal conduit (RMC, GRC)

12.882 sq in × 40 % = 5.1528 sq in allowed. ÷ 0.1562 sq in per wire = 32.99, which Note 7 rounds up to 33 because the decimal is 0.8 or more.

33 #1 THHN in 4" Rigid, drawn to scale

This pull in numbers

33 wires fill
40.0 % of 4" Rigid
Limit for three or more
40 %
For 34 or more
5" Rigid, up to 51
Pipe to wire diameter
9.08 to 1
In THW insulation
27 fit
In XHHW-2 insulation
33 fit