ConduitCount

How many #1 THHN fit in 3-1/2" Rigid?

251 AWG THHN/THWN-2 wires in 3-1/2" Rigid metal conduit (RMC, GRC)

10.010 sq in × 40 % = 4.0040 sq in allowed. ÷ 0.1562 sq in per wire = 25.63, so 25.

25 #1 THHN in 3-1/2" Rigid, drawn to scale

This pull in numbers

25 wires fill
39.0 % of 3-1/2" Rigid
Limit for three or more
40 %
For 26 or more
4" Rigid, up to 33
Pipe to wire diameter
8.00 to 1
In THW insulation
21 fit
In XHHW-2 insulation
26 fit

Before you pull 25

#1 THHN in other 3-1/2" conduit

#1 THHN in other Rigid sizes

Other wire sizes in 3-1/2" Rigid

Charts