ConduitCount

How many #1 THHN fit in 3" Rigid?

191 AWG THHN/THWN-2 wires in 3" Rigid metal conduit (RMC, GRC)

7.499 sq in × 40 % = 2.9996 sq in allowed. ÷ 0.1562 sq in per wire = 19.20, so 19.

19 #1 THHN in 3" Rigid, drawn to scale

This pull in numbers

19 wires fill
39.6 % of 3" Rigid
Limit for three or more
40 %
For 20 or more
3-1/2" Rigid, up to 25
Pipe to wire diameter
6.93 to 1
In THW insulation
15 fit
In XHHW-2 insulation
19 fit

Before you pull 19

#1 THHN in other 3" conduit

#1 THHN in other Rigid sizes

Other wire sizes in 3" Rigid

Charts