ConduitCount

How many #1 THHN fit in 4" IMC?

351 AWG THHN/THWN-2 wires in 4" Intermediate metal conduit

13.631 sq in × 40 % = 5.4524 sq in allowed. ÷ 0.1562 sq in per wire = 34.91, which Note 7 rounds up to 35 because the decimal is 0.8 or more.

35 #1 THHN in 4" IMC, drawn to scale

This pull in numbers

35 wires fill
40.1 % of 4" IMC
Limit for three or more
40 %
For 36 or more
no bigger IMC
Pipe to wire diameter
9.34 to 1
In THW insulation
28 fit
In XHHW-2 insulation
35 fit

Before you pull 35

#1 THHN in other 4" conduit

#1 THHN in other IMC sizes

Other wire sizes in 4" IMC

Charts