ConduitCount

How many #1 THHN fit in 2-1/2" IMC?

131 AWG THHN/THWN-2 wires in 2-1/2" Intermediate metal conduit

5.135 sq in × 40 % = 2.0540 sq in allowed. ÷ 0.1562 sq in per wire = 13.15, so 13.

13 #1 THHN in 2-1/2" IMC, drawn to scale

This pull in numbers

13 wires fill
39.5 % of 2-1/2" IMC
Limit for three or more
40 %
For 14 or more
3" IMC, up to 20
Pipe to wire diameter
5.73 to 1
In THW insulation
11 fit
In XHHW-2 insulation
13 fit

Before you pull 13

#1 THHN in other 2-1/2" conduit

#1 THHN in other IMC sizes

Other wire sizes in 2-1/2" IMC

Charts