ConduitCount

How many #1 THHN fit in 3-1/2" IMC?

271 AWG THHN/THWN-2 wires in 3-1/2" Intermediate metal conduit

10.584 sq in × 40 % = 4.2336 sq in allowed. ÷ 0.1562 sq in per wire = 27.10, so 27.

27 #1 THHN in 3-1/2" IMC, drawn to scale

This pull in numbers

27 wires fill
39.8 % of 3-1/2" IMC
Limit for three or more
40 %
For 28 or more
4" IMC, up to 35
Pipe to wire diameter
8.23 to 1
In THW insulation
22 fit
In XHHW-2 insulation
27 fit

Before you pull 27

#1 THHN in other 3-1/2" conduit

#1 THHN in other IMC sizes

Other wire sizes in 3-1/2" IMC

Charts