How many #10 THHN fit in 1-1/2" Rigid?
3910 AWG THHN/THWN-2 wires in 1-1/2" Rigid metal conduit (RMC, GRC)
2.071 sq in × 40 % = 0.8284 sq in allowed. ÷ 0.0211 sq in per wire = 39.26, so 39.
This pull in numbers
- 39 wires fill
- 39.7 % of 1-1/2" Rigid
- Limit for three or more
- 40 %
- For 40 or more
- 2" Rigid, up to 64
- Pipe to wire diameter
- 9.90 to 1
- In THW insulation
- 34 fit
- In XHHW-2 insulation
- 34 fit
Before you pull 39
- The ground counts. Every wire in the pipe counts toward fill, the green or bare ground and the neutrals too. 39 is the total, not the hots.
- Derating. If all 39 were current-carrying, each would be adjusted to 40 % of its ampacity (Table 310.15(C)(1)): a #10 THHN at 40 A in the 90 °C column becomes 16 A. Grounds don't count as current-carrying. How derating works
- Bends. A full pipe pulls hard. Keep to 360° of bends between pull points, less for a tight fill.
#10 THHN in other 1-1/2" conduit
| Conduit | Inside area | Most #10 THHN |
|---|---|---|
| Electrical metallic tubing | 2.036 | 38 |
| Intermediate metal conduit | 2.225 | 42 |
| Rigid metal conduit (RMC, GRC) | 2.071 | 39 |
| Rigid PVC conduit, Schedule 40 | 1.986 | 37 |
| Rigid PVC conduit, Schedule 80 | 1.711 | 32 |
| Flexible metal conduit (FMC, Greenfield) | 1.858 | 35 |
| Liquidtight flexible metal conduit (LFMC) | 1.981 | 37 |
| Electrical nonmetallic tubing (smurf tube) | 1.986 | 37 |
#10 THHN in other Rigid sizes
Other wire sizes in 1-1/2" Rigid
#14: 85#12: 62#10: 39#8: 22#6: 16#4: 10#3: 8#2: 7#1: 5#1/0: 4#2/0: 3#3/0: 3#4/0: 1250 kcmil: 1300 kcmil: 1350 kcmil: 1500 kcmil: 1