ConduitCount

How many #10 THHN fit in 1-1/2" IMC?

4210 AWG THHN/THWN-2 wires in 1-1/2" Intermediate metal conduit

2.225 sq in × 40 % = 0.8900 sq in allowed. ÷ 0.0211 sq in per wire = 42.18, so 42.

42 #10 THHN in 1-1/2" IMC, drawn to scale

This pull in numbers

42 wires fill
39.8 % of 1-1/2" IMC
Limit for three or more
40 %
For 43 or more
2" IMC, up to 69
Pipe to wire diameter
10.26 to 1
In THW insulation
36 fit
In XHHW-2 insulation
36 fit

Before you pull 42

#10 THHN in other 1-1/2" conduit

#10 THHN in other IMC sizes

Other wire sizes in 1-1/2" IMC

Charts