ConduitCount

How many #10 THHN fit in 2-1/2" Rigid?

9210 AWG THHN/THWN-2 wires in 2-1/2" Rigid metal conduit (RMC, GRC)

4.866 sq in × 40 % = 1.9464 sq in allowed. ÷ 0.0211 sq in per wire = 92.25, so 92.

92 #10 THHN in 2-1/2" Rigid, drawn to scale

This pull in numbers

92 wires fill
39.9 % of 2-1/2" Rigid
Limit for three or more
40 %
For 93 or more
3" Rigid, up to 142
Pipe to wire diameter
15.18 to 1
In THW insulation
80 fit
In XHHW-2 insulation
80 fit

Before you pull 92

#10 THHN in other 2-1/2" conduit

#10 THHN in other Rigid sizes

Other wire sizes in 2-1/2" Rigid

Charts