ConduitCount

How many #10 THHN fit in 2-1/2" IMC?

9710 AWG THHN/THWN-2 wires in 2-1/2" Intermediate metal conduit

5.135 sq in × 40 % = 2.0540 sq in allowed. ÷ 0.0211 sq in per wire = 97.35, so 97.

97 #10 THHN in 2-1/2" IMC, drawn to scale

This pull in numbers

97 wires fill
39.9 % of 2-1/2" IMC
Limit for three or more
40 %
For 98 or more
3" IMC, up to 150
Pipe to wire diameter
15.59 to 1
In THW insulation
84 fit
In XHHW-2 insulation
84 fit

Before you pull 97

#10 THHN in other 2-1/2" conduit

#10 THHN in other IMC sizes

Other wire sizes in 2-1/2" IMC

Charts