ConduitCount

How many #10 THHN fit in 3" Rigid?

14210 AWG THHN/THWN-2 wires in 3" Rigid metal conduit (RMC, GRC)

7.499 sq in × 40 % = 2.9996 sq in allowed. ÷ 0.0211 sq in per wire = 142.16, so 142.

142 #10 THHN in 3" Rigid, drawn to scale

This pull in numbers

142 wires fill
40.0 % of 3" Rigid
Limit for three or more
40 %
For 143 or more
3-1/2" Rigid, up to 189
Pipe to wire diameter
18.84 to 1
In THW insulation
123 fit
In XHHW-2 insulation
123 fit

Before you pull 142

#10 THHN in other 3" conduit

#10 THHN in other Rigid sizes

Other wire sizes in 3" Rigid

Charts