ConduitCount

How many #2 THHN fit in 3-1/2" PVC Sch 80?

302 AWG THHN/THWN-2 wires in 3-1/2" Rigid PVC conduit, Schedule 80

8.688 sq in × 40 % = 3.4752 sq in allowed. ÷ 0.1158 sq in per wire = 30.01, so 30.

30 #2 THHN in 3-1/2" PVC Sch 80, drawn to scale

This pull in numbers

30 wires fill
40.0 % of 3-1/2" PVC Sch 80
Limit for three or more
40 %
For 31 or more
4" PVC Sch 80, up to 39
Pipe to wire diameter
8.66 to 1
In THW insulation
26 fit
In XHHW-2 insulation
30 fit

Before you pull 30

#2 THHN in other 3-1/2" conduit

#2 THHN in other PVC Sch 80 sizes

Other wire sizes in 3-1/2" PVC Sch 80

Charts