ConduitCount

How many 300 kcmil THHN fit in 1-1/2" Rigid?

1300 kcmil THHN/THWN-2 wires in 1-1/2" Rigid metal conduit (RMC, GRC)

2.071 sq in × 53 % = 1.0976 sq in allowed. ÷ 0.4608 sq in per wire = 2.38.

1 300 kcmil THHN in 1-1/2" Rigid, drawn to scale

This pull in numbers

1 wires fill
22.3 % of 1-1/2" Rigid
Limit for one
53 %
For 2 or more
2" Rigid, up to 3
Pipe to wire diameter
2.12 to 1
In THW insulation
1 fit
In XHHW-2 insulation
1 fit

Before you pull 1

300 kcmil THHN in other 1-1/2" conduit

300 kcmil THHN in other Rigid sizes

Other wire sizes in 1-1/2" Rigid

Charts