ConduitCount

How many 300 kcmil THHN fit in 1-1/2" IMC?

1300 kcmil THHN/THWN-2 wires in 1-1/2" Intermediate metal conduit

2.225 sq in × 53 % = 1.1793 sq in allowed. ÷ 0.4608 sq in per wire = 2.56.

1 300 kcmil THHN in 1-1/2" IMC, drawn to scale

This pull in numbers

1 wires fill
20.7 % of 1-1/2" IMC
Limit for one
53 %
For 2 or more
2" IMC, up to 3
Pipe to wire diameter
2.20 to 1
In THW insulation
1 fit
In XHHW-2 insulation
1 fit

Before you pull 1

300 kcmil THHN in other 1-1/2" conduit

300 kcmil THHN in other IMC sizes

Other wire sizes in 1-1/2" IMC

Charts