How many 300 kcmil THHN fit in 2" IMC?

3300 kcmil THHN/THWN-2 wires in 2" Intermediate metal conduit

3.630 sq in × 40 % = 1.4520 sq in allowed. ÷ 0.4608 sq in per wire = 3.15, so 3.

3 300 kcmil THHN in 2" IMC, drawn to scale

This pull in numbers

3 wires fill
38.1 % of 2" IMC
Limit for three or more
40 %
For 4 or more
2-1/2" IMC, up to 4
Pipe to wire diameter
2.81 to 1
In THW insulation
2 fit
In XHHW-2 insulation
3 fit

The pipe is 2.81 times the wire's diameter, inside the 2.8 to 3.2 range where three wires can wedge side by side on a pull. If you pull exactly three, go up a size or pull with care.