ConduitCount

How many #4 THHN fit in 2" IMC?

174 AWG THHN/THWN-2 wires in 2" Intermediate metal conduit

3.630 sq in × 40 % = 1.4520 sq in allowed. ÷ 0.0824 sq in per wire = 17.62, so 17.

17 #4 THHN in 2" IMC, drawn to scale

This pull in numbers

17 wires fill
38.6 % of 2" IMC
Limit for three or more
40 %
For 18 or more
2-1/2" IMC, up to 25
Pipe to wire diameter
6.64 to 1
In THW insulation
15 fit
In XHHW-2 insulation
18 fit

Before you pull 17

#4 THHN in other 2" conduit

#4 THHN in other IMC sizes

Other wire sizes in 2" IMC

Charts