ConduitCount

How many #4 THHN fit in 3" IMC?

384 AWG THHN/THWN-2 wires in 3" Intermediate metal conduit

7.922 sq in × 40 % = 3.1688 sq in allowed. ÷ 0.0824 sq in per wire = 38.46, so 38.

38 #4 THHN in 3" IMC, drawn to scale

This pull in numbers

38 wires fill
39.5 % of 3" IMC
Limit for three or more
40 %
For 39 or more
3-1/2" IMC, up to 51
Pipe to wire diameter
9.80 to 1
In THW insulation
32 fit
In XHHW-2 insulation
39 fit

Before you pull 38

#4 THHN in other 3" conduit

#4 THHN in other IMC sizes

Other wire sizes in 3" IMC

Charts