ConduitCount

How many 350 kcmil THHN fit in 2" IMC?

2350 kcmil THHN/THWN-2 wires in 2" Intermediate metal conduit

3.630 sq in × 31 % = 1.1253 sq in allowed. ÷ 0.5242 sq in per wire = 2.15.

2 350 kcmil THHN in 2" IMC, drawn to scale

This pull in numbers

2 wires fill
28.9 % of 2" IMC
Limit for two
31 %
For 3 or more
2-1/2" IMC, up to 4
Pipe to wire diameter
2.63 to 1
In THW insulation
1 fit
In XHHW-2 insulation
3 fit

Before you pull 2

350 kcmil THHN in other 2" conduit

350 kcmil THHN in other IMC sizes

Other wire sizes in 2" IMC

Charts