ConduitCount

How many #6 THHN fit in 3" Rigid?

596 AWG THHN/THWN-2 wires in 3" Rigid metal conduit (RMC, GRC)

7.499 sq in × 40 % = 2.9996 sq in allowed. ÷ 0.0507 sq in per wire = 59.16, so 59.

59 #6 THHN in 3" Rigid, drawn to scale

This pull in numbers

59 wires fill
39.9 % of 3" Rigid
Limit for three or more
40 %
For 60 or more
3-1/2" Rigid, up to 79
Pipe to wire diameter
12.17 to 1
In THW insulation
41 fit
In XHHW-2 insulation
51 fit

Before you pull 59

#6 THHN in other 3" conduit

#6 THHN in other Rigid sizes

Other wire sizes in 3" Rigid

Charts