ConduitCount

How many #10 THHN fit in 3-1/2" IMC?

20010 AWG THHN/THWN-2 wires in 3-1/2" Intermediate metal conduit

10.584 sq in × 40 % = 4.2336 sq in allowed. ÷ 0.0211 sq in per wire = 200.64, so 200.

200 #10 THHN in 3-1/2" IMC, drawn to scale

This pull in numbers

200 wires fill
39.9 % of 3-1/2" IMC
Limit for three or more
40 %
For 201 or more
4" IMC, up to 258
Pipe to wire diameter
22.38 to 1
In THW insulation
174 fit
In XHHW-2 insulation
174 fit

Before you pull 200

#10 THHN in other 3-1/2" conduit

ConduitInside areaMost #10 THHN
Electrical metallic tubing11.545219
Intermediate metal conduit10.584200
Rigid metal conduit (RMC, GRC)10.010189
Rigid PVC conduit, Schedule 409.737184
Rigid PVC conduit, Schedule 808.688164
Flexible metal conduit (FMC, Greenfield)9.621182
Liquidtight flexible metal conduit (LFMC)9.731184

#10 THHN in other IMC sizes

Other wire sizes in 3-1/2" IMC

Charts