How many #10 THHN fit in 3-1/2" Rigid?
18910 AWG THHN/THWN-2 wires in 3-1/2" Rigid metal conduit (RMC, GRC)
10.010 sq in × 40 % = 4.0040 sq in allowed. ÷ 0.0211 sq in per wire = 189.76, so 189.
This pull in numbers
- 189 wires fill
- 39.8 % of 3-1/2" Rigid
- Limit for three or more
- 40 %
- For 190 or more
- 4" Rigid, up to 244
- Pipe to wire diameter
- 21.77 to 1
- In THW insulation
- 164 fit
- In XHHW-2 insulation
- 164 fit
Before you pull 189
- The ground counts. Every wire in the pipe counts toward fill, the green or bare ground and the neutrals too. 189 is the total, not the hots.
- Derating. If all 189 were current-carrying, each would be adjusted to 35 % of its ampacity (Table 310.15(C)(1)): a #10 THHN at 40 A in the 90 °C column becomes 14 A. Grounds don't count as current-carrying. How derating works
- Bends. A full pipe pulls hard. Keep to 360° of bends between pull points, less for a tight fill.
#10 THHN in other 3-1/2" conduit
| Conduit | Inside area | Most #10 THHN |
|---|---|---|
| Electrical metallic tubing | 11.545 | 219 |
| Intermediate metal conduit | 10.584 | 200 |
| Rigid metal conduit (RMC, GRC) | 10.010 | 189 |
| Rigid PVC conduit, Schedule 40 | 9.737 | 184 |
| Rigid PVC conduit, Schedule 80 | 8.688 | 164 |
| Flexible metal conduit (FMC, Greenfield) | 9.621 | 182 |
| Liquidtight flexible metal conduit (LFMC) | 9.731 | 184 |
#10 THHN in other Rigid sizes
Other wire sizes in 3-1/2" Rigid
#10: 189#8: 109#6: 79#4: 48#3: 41#2: 34#1: 25#1/0: 21#2/0: 18#3/0: 15#4/0: 12250 kcmil: 10300 kcmil: 8350 kcmil: 7500 kcmil: 5