How many 250 kcmil THHN fit in 3-1/2" PVC Sch 80?
8250 kcmil THHN/THWN-2 wires in 3-1/2" Rigid PVC conduit, Schedule 80
8.688 sq in × 40 % = 3.4752 sq in allowed. ÷ 0.3970 sq in per wire = 8.75, so 8.
This pull in numbers
- 8 wires fill
- 36.6 % of 3-1/2" PVC Sch 80
- Limit for three or more
- 40 %
- For 9 or more
- 4" PVC Sch 80, up to 11
- Pipe to wire diameter
- 4.68 to 1
- In THW insulation
- 7 fit
- In XHHW-2 insulation
- 9 fit
Before you pull 8
- The ground counts. Every wire in the pipe counts toward fill, the green or bare ground and the neutrals too. 8 is the total, not the hots.
- Derating. If all 8 were current-carrying, each would be adjusted to 70 % of its ampacity (Table 310.15(C)(1)): a 250 kcmil THHN at 290 A in the 90 °C column becomes 203 A. Grounds don't count as current-carrying. How derating works
- Bends. A full pipe pulls hard. Keep to 360° of bends between pull points, less for a tight fill.
250 kcmil THHN in other 3-1/2" conduit
| Conduit | Inside area | Most 250 kcmil THHN |
|---|---|---|
| Electrical metallic tubing | 11.545 | 11 |
| Intermediate metal conduit | 10.584 | 10 |
| Rigid metal conduit (RMC, GRC) | 10.010 | 10 |
| Rigid PVC conduit, Schedule 40 | 9.737 | 10 |
| Rigid PVC conduit, Schedule 80 | 8.688 | 8 |
| Flexible metal conduit (FMC, Greenfield) | 9.621 | 9 |
| Liquidtight flexible metal conduit (LFMC) | 9.731 | 10 |
250 kcmil THHN in other PVC Sch 80 sizes
Other wire sizes in 3-1/2" PVC Sch 80
#10: 164#8: 95#6: 68#4: 42#3: 35#2: 30#1: 22#1/0: 18#2/0: 15#3/0: 13#4/0: 10250 kcmil: 8300 kcmil: 7350 kcmil: 6500 kcmil: 5