796 AWG THHN/THWN-2 wires in 3-1/2" Rigid metal conduit (RMC, GRC)

10.010 sq in × 40 % = 4.0040 sq in allowed. ÷ 0.0507 sq in per wire = 78.97, which Note 7 rounds up to 79 because the decimal is 0.8 or more.

79 #6 THHN in 3-1/2" Rigid, drawn to scale

This pull in numbers

79 wires fill
40.0 % of 3-1/2" Rigid
Limit for three or more
40 %
For 80 or more
4" Rigid, up to 101
Pipe to wire diameter
14.06 to 1
In THW insulation
55 fit
In XHHW-2 insulation
68 fit

Before you pull 79

#6 THHN in other 3-1/2" conduit

#6 THHN in other Rigid sizes