ConduitCount

How many #1/0 THHN fit in 1-1/2" IMC?

41/0 AWG THHN/THWN-2 wires in 1-1/2" Intermediate metal conduit

2.225 sq in × 40 % = 0.8900 sq in allowed. ÷ 0.1855 sq in per wire = 4.80, so 4.

4 #1/0 THHN in 1-1/2" IMC, drawn to scale

This pull in numbers

4 wires fill
33.3 % of 1-1/2" IMC
Limit for three or more
40 %
For 5 or more
2" IMC, up to 8
Pipe to wire diameter
3.46 to 1
In THW insulation
4 fit
In XHHW-2 insulation
5 fit

Before you pull 4

#1/0 THHN in other 1-1/2" conduit

#1/0 THHN in other IMC sizes

Other wire sizes in 1-1/2" IMC

Charts