ConduitCount

How many #10 THHN fit in 3-1/2" PVC Sch 40?

18410 AWG THHN/THWN-2 wires in 3-1/2" Rigid PVC conduit, Schedule 40

9.737 sq in × 40 % = 3.8948 sq in allowed. ÷ 0.0211 sq in per wire = 184.59, so 184.

184 #10 THHN in 3-1/2" PVC Sch 40, drawn to scale

This pull in numbers

184 wires fill
39.9 % of 3-1/2" PVC Sch 40
Limit for three or more
40 %
For 185 or more
4" PVC Sch 40, up to 238
Pipe to wire diameter
21.47 to 1
In THW insulation
160 fit
In XHHW-2 insulation
160 fit

Before you pull 184

#10 THHN in other 3-1/2" conduit

ConduitInside areaMost #10 THHN
Electrical metallic tubing11.545219
Intermediate metal conduit10.584200
Rigid metal conduit (RMC, GRC)10.010189
Rigid PVC conduit, Schedule 409.737184
Rigid PVC conduit, Schedule 808.688164
Flexible metal conduit (FMC, Greenfield)9.621182
Liquidtight flexible metal conduit (LFMC)9.731184

#10 THHN in other PVC Sch 40 sizes

Other wire sizes in 3-1/2" PVC Sch 40

Charts