ConduitCount

How many 250 kcmil THHN fit in 2-1/2" IMC?

5250 kcmil THHN/THWN-2 wires in 2-1/2" Intermediate metal conduit

5.135 sq in × 40 % = 2.0540 sq in allowed. ÷ 0.3970 sq in per wire = 5.17, so 5.

5 250 kcmil THHN in 2-1/2" IMC, drawn to scale

This pull in numbers

5 wires fill
38.7 % of 2-1/2" IMC
Limit for three or more
40 %
For 6 or more
3" IMC, up to 8
Pipe to wire diameter
3.60 to 1
In THW insulation
4 fit
In XHHW-2 insulation
5 fit

Before you pull 5

250 kcmil THHN in other 2-1/2" conduit

250 kcmil THHN in other IMC sizes

Other wire sizes in 2-1/2" IMC

Charts