ConduitCount

How many #6 THHN fit in 3-1/2" PVC Sch 80?

686 AWG THHN/THWN-2 wires in 3-1/2" Rigid PVC conduit, Schedule 80

8.688 sq in × 40 % = 3.4752 sq in allowed. ÷ 0.0507 sq in per wire = 68.54, so 68.

68 #6 THHN in 3-1/2" PVC Sch 80, drawn to scale

This pull in numbers

68 wires fill
39.7 % of 3-1/2" PVC Sch 80
Limit for three or more
40 %
For 69 or more
4" PVC Sch 80, up to 89
Pipe to wire diameter
13.09 to 1
In THW insulation
48 fit
In XHHW-2 insulation
59 fit

Before you pull 68

#6 THHN in other 3-1/2" conduit

#6 THHN in other PVC Sch 80 sizes

Other wire sizes in 3-1/2" PVC Sch 80

Charts