4" Rigid conduit fill
4" Rigid metal conduit (RMC, GRC) has an inside area of 12.882 sq in (4.050 in across). Three or more wires may take 40 % of it: 5.1528 sq in.
- One wire, 53 %
- 6.8275 sq in
- Two wires, 31 %
- 3.9934 sq in
- Three or more, 40 %
- 5.1528 sq in
- Nipple, 60 %
- 7.7292 sq in
- Support
- Every 10 ft, 3 ft from boxes
- Sold in
- 10 ft sticks
How many wires fit in 4" Rigid
All wires the same size and type, by Annex C's method. For a mix of sizes, open the calculator.
| Wire size | THHN/THWN-2 | XHHW-2 | THW/THW-2 |
|---|---|---|---|
| 14 AWG | 531 | 370 | 370 |
| 12 AWG | 387 | 284 | 284 |
| 10 AWG | 244 | 212 | 212 |
| 8 AWG | 140 | 118 | 118 |
| 6 AWG | 101 | 87 | 71 |
| 4 AWG | 62 | 63 | 53 |
| 3 AWG | 53 | 53 | 45 |
| 2 AWG | 44 | 45 | 38 |
| 1 AWG | 33 | 33 | 27 |
| 1/0 AWG | 27 | 28 | 23 |
| 2/0 AWG | 23 | 23 | 19 |
| 3/0 AWG | 19 | 19 | 16 |
| 4/0 AWG | 16 | 16 | 14 |
| 250 kcmil | 13 | 13 | 11 |
| 300 kcmil | 11 | 11 | 9 |
| 350 kcmil | 10 | 10 | 8 |
| 400 kcmil | 8 | 9 | 7 |
| 500 kcmil | 7 | 7 | 6 |
| 600 kcmil | 6 | 6 | 5 |
| 700 kcmil | 5 | 5 | 4 |
| 750 kcmil | 5 | 5 | 4 |
| 800 kcmil | 4 | 4 | 4 |
| 900 kcmil | 4 | 4 | 3 |
| 1000 kcmil | 4 | 4 | 3 |
Other 4" conduit
| Conduit | Inside area | #14 | #12 | #10 | #8 | #6 |
|---|---|---|---|---|---|---|
| Rigid metal conduit (RMC, GRC) | 12.882 | 531 | 387 | 244 | 140 | 101 |
| Electrical metallic tubing | 14.753 | 608 | 443 | 279 | 161 | 116 |
| Intermediate metal conduit | 13.631 | 562 | 410 | 258 | 149 | 107 |
| Rigid PVC conduit, Schedule 40 | 12.554 | 517 | 377 | 238 | 137 | 99 |
| Rigid PVC conduit, Schedule 80 | 11.258 | 464 | 338 | 213 | 123 | 89 |
| Flexible metal conduit (FMC, Greenfield) | 12.566 | 518 | 378 | 238 | 137 | 99 |
| Liquidtight flexible metal conduit (LFMC) | 12.692 | 523 | 381 | 240 | 138 | 100 |
About Rigid
Rigid (galvanized rigid conduit, GRC) has the thickest wall and the least room inside of the steel types. Support follows 344.30: within 3 ft of each box, then every 10 ft, or longer on straight runs with threaded couplings (Table 344.30(B)(2)). See strap spacing and the fill rules.