ConduitCount

How many #1/0 THHN fit in 2-1/2" IMC?

111/0 AWG THHN/THWN-2 wires in 2-1/2" Intermediate metal conduit

5.135 sq in × 40 % = 2.0540 sq in allowed. ÷ 0.1855 sq in per wire = 11.07, so 11.

11 #1/0 THHN in 2-1/2" IMC, drawn to scale

This pull in numbers

11 wires fill
39.7 % of 2-1/2" IMC
Limit for three or more
40 %
For 12 or more
3" IMC, up to 17
Pipe to wire diameter
5.26 to 1
In THW insulation
9 fit
In XHHW-2 insulation
11 fit

Before you pull 11

#1/0 THHN in other 2-1/2" conduit

#1/0 THHN in other IMC sizes

Other wire sizes in 2-1/2" IMC

Charts