How many #1/0 THHN fit in 4" IMC?
291/0 AWG THHN/THWN-2 wires in 4" Intermediate metal conduit
13.631 sq in × 40 % = 5.4524 sq in allowed. ÷ 0.1855 sq in per wire = 29.39, so 29.
This pull in numbers
- 29 wires fill
- 39.5 % of 4" IMC
- Limit for three or more
- 40 %
- For 30 or more
- no bigger IMC
- Pipe to wire diameter
- 8.57 to 1
- In THW insulation
- 24 fit
- In XHHW-2 insulation
- 30 fit
Before you pull 29
- The ground counts. Every wire in the pipe counts toward fill, the green or bare ground and the neutrals too. 29 is the total, not the hots.
- Derating. If all 29 were current-carrying, each would be adjusted to 45 % of its ampacity (Table 310.15(C)(1)): a #1/0 THHN at 170 A in the 90 °C column becomes 76.5 A. Grounds don't count as current-carrying. How derating works
- Bends. A full pipe pulls hard. Keep to 360° of bends between pull points, less for a tight fill.
#1/0 THHN in other 4" conduit
| Conduit | Inside area | Most #1/0 THHN |
|---|---|---|
| Electrical metallic tubing | 14.753 | 32 |
| Intermediate metal conduit | 13.631 | 29 |
| Rigid metal conduit (RMC, GRC) | 12.882 | 27 |
| Rigid PVC conduit, Schedule 40 | 12.554 | 27 |
| Rigid PVC conduit, Schedule 80 | 11.258 | 24 |
| Flexible metal conduit (FMC, Greenfield) | 12.566 | 27 |
| Liquidtight flexible metal conduit (LFMC) | 12.692 | 27 |
#1/0 THHN in other IMC sizes
Other wire sizes in 4" IMC
#8: 149#6: 107#4: 66#3: 56#2: 47#1: 35#1/0: 29#2/0: 24#3/0: 20#4/0: 17250 kcmil: 13300 kcmil: 12350 kcmil: 10500 kcmil: 7