ConduitCount

How many #1/0 THHN fit in 4" IMC?

291/0 AWG THHN/THWN-2 wires in 4" Intermediate metal conduit

13.631 sq in × 40 % = 5.4524 sq in allowed. ÷ 0.1855 sq in per wire = 29.39, so 29.

29 #1/0 THHN in 4" IMC, drawn to scale

This pull in numbers

29 wires fill
39.5 % of 4" IMC
Limit for three or more
40 %
For 30 or more
no bigger IMC
Pipe to wire diameter
8.57 to 1
In THW insulation
24 fit
In XHHW-2 insulation
30 fit

Before you pull 29

#1/0 THHN in other 4" conduit

#1/0 THHN in other IMC sizes

Other wire sizes in 4" IMC

Charts